Below are the first 10 and last 10 pages of uncorrected machine-read text (when available) of this chapter, followed by the top 30 algorithmically extracted key phrases from the chapter as a whole.
Intended to provide our own search engines and external engines with highly rich, chapter-representative searchable text on the opening pages of each chapter.
Because it is UNCORRECTED material, please consider the following text as a useful but insufficient proxy for the authoritative book pages.
Do not use for reproduction, copying, pasting, or reading; exclusively for search engines.
OCR for page 160
161
APPENDIX F
Comparison of National and International Standards Requirements
F1 Tunnel Ventilation
This section provides comparison tables on tunnel ventilation requirements in different national and international standards.
It covers Natural Ventilation (Table F1-1), Longitudinal Ventilation (Table F1-2), Transverse Ventilation (Table F1-3),
and Emergency Exits Pressurization requirements (Table F1-4).
TABLE F1-1
NATURAL VENTILATION (NFPA 502, 56, 77)
Country/ Requirement
Guideline
France/ 3.2.2 Arrangements for smoke ventilation will be required for tunnels in
Circ2000- excess of the following lengths: 300 m (984.3 ft) in the case of urban tunnels,
63A2 500 m (1,640.4 ft) in the case of non-urban tunnels which are not for light
traffic (...800 m or 2,624.7 ft provided that the absence of ventilation is
compensated ...), 1,000 m (3,280.8 ft) for light traffic tunnels.
Switzerland/ Natural ventilation (piston effect) is sufficient for bidirectional traffic tunnels
Design < 200 m (656.2 ft)
- one directional traffic tunnels several hundred meters decision/calculation
see guideline "Ventilation of Road Tunnels"
Switzerland/ Contains a decision system which of the three main categories--natural,
Ventilation mechanical without extraction, mechanical with extraction--becomes
necessary.
Decision criteria are:
- traffic type and volume
- tunnel length
- tunnel gradient
It also contains parameters and methods for a detailed calculation of the
chosen system. The calculation systems for normal and emergency case
operation are described, including fire loads.
Germany/ 2.3.3.3 .... In short tunnels it is less reasonable to control the smoke with
RABT ventilators. For that reason tunnels shorter than 400 m (1,312.3 ft) resp. 600 m
(1,968.5 ft) do not have fire ventilation...
Austria/RVS RVS 9.261 Permitted if the fresh air demand during normal operation is
ensured and the length of the escape routes is within the limits.
Norway 601 ... For tunnels shorter than 250 m (820.2 ft) only safety equipment in
terms of lighting is required. ...
UK/BD78/99 5.13 In many short one-way tunnels, of up to 300 m (984.3 ft) length, the
`piston effect' of vehicle induced air flow will provide satisfactory natural
ventilation for normal environmental needs, also emergency evacuation routes
to places of refuge can be made acceptably short ...
5.78 ... Except for shorter tunnels ..., a lack of positive control of smoke
direction is not acceptable...
Japan For tunnels over 1500 m for class AA tunnels, either ventilation system or
parallel escape tube should be provided.
NFPA 502 10.1.1* Emergency ventilation shall not be required in tunnels exceeding
(2008 edition) 240 m (800 ft) in length, where it can be shown by an engineering analysis,
using the design parameters for a particular tunnel (length, cross-section, grade,
prevailing wind, traffic direction, types of cargoes, design fire size, etc.), that
the level of safety provided by a mechanical ventilation system can be equaled
or exceeded by enhancing the means of egress, the use of natural ventilation,
or the use of smoke storage and shall be permitted only where approved by the
authority having jurisdiction.
I.1 Some short tunnels are ventilated naturally (without fans); however, such
tunnels could necessitate a ventilation system to combat a fire emergency.
(continued on next page)
OCR for page 161
162
TABLE F1-1
(continued )
Country/ Requirement
Guideline
Netherlands/NL- 12.1 For tunnels shorter than 250 m (820.2 ft) mechanical ventilation is not
Safe required. Due to the short time for escape it is important that the possibilities
and measures (for escape) are sufficient in relation to the choice of natural
ventilation.
Tunnel constructions of more than >250 m (820.2 ft) and less than <500 m
(1,640.4 ft) offer the possibility to opt for natural ventilation or mechanic
ventilation. Tunnels longer than 500 m (1,640.4 ft) always need a mechanic
ventilation system.
12.2 For natural ventilation the closed structure must be short or techniques of
horizontal slots in the roof or dampers must be applied.
TABLE F1-2
LONGITUDINAL VENTILATION (NFPA 502, 77)
Country/ Requirement
Guideline
France/ 3.2.2 ... Longitudinal ventilation is possible for non-urban one-way tunnels:
Circ2000- up to a length of 5000 m (16,404.2 ft); urban one-way tunnels up to 500 m
63A2 (1,640.4 ft)...(for light traffic up to 800 m or 2,624.7 ft); non-urban two-way
tunnels: up to 1000 m (3,280.8 ft) (for light traffic up to 1,500 m or 4,921.3 ft).
Longitudinal ventilation is prohibited for urban two-way tunnels.
The ventilation must be started up as soon as possible under conditions that
will make it possible to achieve at least 3 m/s (591 fpm) in the direction of
traffic movement. (For urban tunnels or two-way tunnels the ventilation
control may be more delicate in order to maintain stratification).
Switzerland/ Two types are described:
Ventilation Longitudinal ventilation without extraction
Longitudinal ventilation with extraction through a separate channel with
steerable flaps
Decision and calculation system, see guideline "Ventilation of Road Tunnels"
Calculation data for jet fans are included
Calculation data for extraction are included
Calculation data for flaps are included
Germany/RABT 2.3.5.1.2 ... In case of fire the longitudinal ventilation can ... be activated to
control the velocity of the smoke.
2.3.3.3 ... For longer tunnels the smoke is discharged through openings in the
ceiling at limited sections or blown in one direction from the site of the fire.
Singular discharge can reduce the smoke spread for long tunnels. For
longitudinal ventilation the traffic situation, the site of the fire, and the velocity
of the tunnel air are decisive for the operation of the ventilation. For
contraflow and congestion the use of longitudinal ventilation is only possible
with limitations. For this reason a risk evaluation must be carried out for
tunnel lengths over 600 m (1,968.5 ft)...
2.3.3.4 Critical air velocity 2.3 to 3.6 m/s (453 to 709 fpm) (indicated in a
table depending on tunnel shape, gradient and fire output).
Austria/RVS RVS 9.261 If natural ventilation does not ensure sufficient supply of fresh air
or if the escape routes are above limits mechanical ventilation is necessary.
Possible systems are longitudinal, semi transversal and transversal.
For dimensioning of the system, normal operation phase and emergency (fire)
operation phase must be taken into account.
The three main aims are:
- Enable self-rescue due to smoke prevention for a sufficient time and
ventilation of escape tubes
- Ensuring reasonable conditions for rescue staff
- Reduction of damage to people, vehicles and tunnel structure
A decision system based on risk factors, a catalogue of measures and special
demands for each ventilation system are given.
(continued on next page)
OCR for page 162
163
TABLE F1-2
(continued )
Country/ Requirement
Guideline
Norway/Road 1004.21 Mechanical longitudinal ventilation is ... based on the use of impulse
Tunnels fans. In long tunnels with heavy traffic, or where there are particular
restrictions..., the use of ventilator shaft may be considered.
1005 ... the ventilation system shall also be designed to control a fire of 5 MW
(17 MBtu/hr) or 20 MW (68 MBtu/hr) depending on the traffic volume...For
tunnels with gradient <2% the net design air velocity shall be a minimum 2 m/s
(394 fpm) for tunnels designed for car fires (5 MW or 17 MBtu/hr) and
minimum 3.5 m/s (689 fpm) for HGV fires (20 MW or 68 MBtu/hr)...
UK/BD78/99 For tunnels of between 300 to 400 m (984.3 to 1,312.3 ft) in length, mechanical
ventilation plant will need to be considered with respect to fire smoke control,
for example, where traffic is relatively light and/or gradients are not steep, the
length of tunnel where mechanical ventilation plant is unlikely to be required
may be increased to 400 m (1,312.3 ft). Mechanical ventilation is required for
all longer (400 m or 1,312.3 ft and over) tunnels and for (200 m or 656 ft and
over) tunnels on steep gradients or those subject to frequent congestion, either
due to high usage or external traffic conditions...
5.16 Longitudinal ventilation is the simplest form of tunnel ventilation and
because of lower capital and running cost benefits is often the first choice. ...
5.91 Fans for tunnel air control shall be reversible ...
5.22 Calculations of jet fan capacity shall take into account that air velocities
shall be sufficient for control of fire smoke.
The fans shall be capable of reverse operation ...
5.74 The initial velocity of smoke layer advance is about 1.3 m/s (256 fpm) for
a 3 MW (10 MBtu/hr) car fire and 3.0 m/s (591 fpm) for a 25 MW (85
MBtu/hr) truck fire, depending on the tunnel geometry. A gasoline tanker fire
of 50 to 100 MW (171 to 341 MBtu/hr) could generate a smoke velocity of
7.0 m/s (1,378 fpm) or more, which requires large and high cost ventilation
plant provisions to be able to cope successfully.
Ventilation normal provision for tunnel class AA, A, B, to be considered for
C, D.
Netherlands/NL- 12.1 Tunnels over 500 m (1,640.4 ft) always need a mechanical ventilation
Safe system... Longitudinal ventilation is suitable for tunnels over 250 m (820.2 ft).
12.2 Longitudinal ventilation is applied only in tubes with one-directional
traffic. The ventilation design has to take into account: the fire intensity, the
location of the fire ..., influence of the wind, the resistance in ventilation by
the vehicles, influence of the longitudinal slope on the draught.
NFPA 502 10.2.4 In tunnels with unidirectional traffic where motorists are likely to be
(2008 edition) located upstream of the fire site, the following objectives shall be met:
(1) Longitudinal systems
(a) Prevent backlayering by producing a longitudinal air velocity that is greater
than the critical velocity in the direction of traffic flow.
(b) Avoid disruption of the smoke layer initially by not operating jet fans that
are located near the fire site. Operate fans that are farthest away from the site
first.
10.4 Design Objectives. The design objectives of the emergency ventilation
system shall be to control, to extract, or to control and extract, smoke and
heated gases as follows:
(2) Longitudinal airflow rates are produced to prevent backlayering of smoke
in a path of egress away from a fire (Annex D provides methodology for
Critical Velocity Calculations).
EU/2004/54/EC 2.9.2 A mechanical ventilation system shall be installed in all tunnels longer
than 1000 m (3,280.8 ft) with traffic volume higher than 2,000 vehicles per
lane. 2.9.3 In tunnels with bidirectional and/or congested unidirectional
traffic, longitudinal ventilation shall be allowed only if a risk analysis
according to Article 13 shows it is acceptable and/or specific measures are
taken, such as appropriate traffic management, shorter emergency exit
distances, smoke exhausts at intervals.
OCR for page 163
164
TABLE F1-3
TRANSVERSE VENTILATION (20, 66)
Country/ Requirement
Guideline
France/ 3.2.2 ...the objectives for transverse ventilation systems are to... retain a layer
Circ2000- of pure air close to the roadway, and to extract smoke ... at roof level. Smoke
63A2 extraction...must be capable of being achieved over a distance of the order of
400 m (1,312 ft) in an urban tunnel and 600 m (1,968 ft) in a non-urban
tunnel.... If fresh air blower blocks are more than 800 m (2,625 ft) long,
provision must be made for the possibility of blowing fresh air into the lower
part of the tunnel under all circumstances.
This imposes a requirement for blower outlets at the base of the side walls and
means for delivering fresh air to the duct feeding them at all times...
The start-up of smoke extraction requires a human presence at all times, or an
automatic system, which includes fire detection. When the tunnel has a human
presence offering rapid and accurate control at all times it is most effective
that smoke is extracted using smoke vents in the roof which are opened under
remote control. Vents are placed per 50 m or 164 ft (not more than 100 m or
328 ft apart in non-urban tunnels).
Switzerland/ Transversal ventilation with one fresh air channel and one extraction channel
Ventilation with adjustable flaps.
Germany/RABT 2.3.5.3 Today the only economical use of transverse ventilation is in cases of
long tunnels...
2.3.5.2 Semi-transverse ventilation... the inlets are placed at the road level in
regular distances 20 m 65.6 ft.
Normally, the inflow velocity can be up to 10 m/s (2,000 fpm). However, it is
not to exceed 3 m/s (591 fpm) when there is a fire. The polluted air is usually
discharged through the portals... For long tunnels semi-transverse ventilation
in sections (point extraction) can be an economical alternative to longitudinal
ventilation...
UK/BD78/99 5.30 Fully transverse ventilation is the most comprehensive form of
mechanical ventilation, but because of its high capital and operational costs, is
seldom adopted for new tunnels.
5.37 Semi transverse ventilation has frequently been used in UK tunnels at
river crossings.
Ventilation normal provision for tunnel class AA, A, B, to be considered for
C, D.
Netherlands/NL- 12.1 When ... traffic intensities and tunnel length increases, also the risk of
Safe congestion increases in case of a (fire) accident.
Transversal ventilation can become an alternative for this. Though warning is
given to this transversal ventilation for its limited capacity of removing smoke
and for its reliability.
A better option would be the creation of open spaces in the tunnel (cutting the
tunnel into several smaller parts).
NFPA 502 10.2.4 In tunnels with unidirectional traffic where motorists are likely to be
(2008 edition) located upstream of the fire site, the following objectives shall be met:
(2) Transverse or reversible semi-transverse systems
(a) Maximize the exhaust rate in the ventilation zone that contains the fire and
minimize the amount of outside air that is introduced by a transverse system.
(b) Create a longitudinal airflow in the direction of traffic flow by operating
the upstream ventilation zone(s) in maximum supply and the downstream
ventilation zone(s) in maximum exhaust.
10.4 Design Objectives. The design objectives of the emergency ventilation
system shall be to control, to extract, or to control and extract, smoke and
heated gases as follows:
(1) A stream of noncontaminated air is provided to motorists in a path of
egress away from a fire.
EU/2004/54/EC 2.9.2 A mechanical ventilation system shall be installed in all tunnels longer
than 1000 m (3,280 ft) with a traffic volume higher than 2,000 vehicles per
lane.
2.9.4 Transverse or semi-transverse ventilation systems shall be used in
tunnels where a mechanical ventilation system is necessary and longitudinal
ventilation is not allowed according to 2.9.3. These systems shall be able to
exhaust smoke in case of fire.
(continued on next page)
OCR for page 164
165
TABLE F1-3
(continued )
Country/ Requirement
Guideline
2.9.5 For tunnels with bi-directional traffic, with a traffic volume higher than
2,000 vehicles per lane, longer than 3000 m (9,842 ft) and with a control
centre and transverse and/or semi-transverse ventilation, the following
minimum measures shall be taken as regards ventilation: Air and smoke
extraction dampers shall be installed which can be operated separately or in
groups. The longitudinal air velocity shall be monitored constantly and the
steering process of the ventilation system (dampers, fans, etc.) adjusted
accordingly.
TABLE F1-4
EMERGENCY EXITS PRESSURIZATION (NFPA 502, 77)
Country/ Requirement
Guideline
France/Circ2000- 3.2.3 a) Communications between tubes: The airlocks provided in the
63A2 communication facilities between tubes must be provided with a ventilation
system providing them with an excess pressure of approximately 80 Pa
(0.0116 psi) with respect to the tube in which an incident or accident has
occurred.
b) Safety tunnel parallel to the tunnel: Whenever in use the tunnel is to be
ventilated and the communication airlocks (or the tunnel itself in the absence
of airlocks) is to have an excess pressure of approximately 80 Pa in
comparison with the tunnel.
c) Shelters: Shelters are to be equipped with a specific ventilation system.
Air quality is to be maintained at all times by renewing the volume in the
shelter three times per hour.
Switzerland/ Separate guideline "Ventilation of Safety- and Cross-passages in Road
Ventilation Tunnels."
Germany/RABT 2.5.1.3 The escape routes must be kept free of smoke. For this purpose locks
or overpressure are useful measures.
UK/BD78/99 3.17 Cross passages and escape shafts ... require ventilation to maintain a
supply of fresh air to the escape route and positive pressure or other
provisions to exclude smoke from any fire within a traffic bore. Where two
or more bores are linked by cross connections, the effect of opening one or
more of those cross connection doors shall be considered.
NFPA 502 (2008 7.14.1.1* The means of egress requirements for all road tunnels and those
edition) roadways beneath air-right structures that the authority having jurisdiction
determines are similar to a road tunnel shall be in accordance with NFPA
101, Chapter 7, except as modified by this standard.
7.14.2 Tenable Environment. A tenable environment shall be provided in
the means of egress during the evacuation phase.
7.14.5.5 The force required to open the doors fully when applied to the
latch side shall be as low as possible, but shall not exceed 222 N (50 lb).
Netherlands/NL- 11.4 ... Escape tubes... must be safe ...control of a smokeless situation in
Safe escape routes.
OCR for page 165
166
F2 Tunnel Ventilation
Appendix F2 provides comparison tables on tunnel fire protection requirements in different national (including NFPA 502,
2008 edition) and international standards. It covers the fire fighting equipment (extinguisher, hose-reels, and so forth) and water
requirements.
TABLE F2-1
FIRE FIGHTING (PORTABLE EXTINGUISHER, HOSE-REELS, AND SO FORTH) AND
WATER REQUIREMENTS (NFPA 502, 56, 77)
Country/ Requirement
Guideline
France/Circ2000- 3.5.1 Two standard portable extinguishers having a recommended unit
63A2 capacity of 6 kg (13.2 lb)... are to be located in the emergency recesses ... It
is recommended that water with additive extinguishers should be used.
2.5 Fire-fighting equipment ...must preferably be located in recesses, which
are separate from emergency recesses.
3.5.2 The provision of a water supply is not compulsory in non-urban
tunnels less than 500 m (1,640 ft) long. In other circumstances, unless
different arrangements are agreed by local authorities, a water pipe is to be
installed. Fire-fighting equipment of the riser or hydrant type delivering 120
m3 (4,238 ft3) at a pressure of 0.6 MPa (87 psi) are to be installed
approximately every 200 m (656 ft). In the case of a tunnel in which there is
a change in level, a range of 0.4 to 0.8 MPa (58 to 116 psi) shall be accepted.
The delivered flow from a hydrant must be 60 m3/h (264 gpm).
Switzerland/ Two 6 kg (13.2 lb) fire extinguishers placed at each emergency telephone
Design station, in bidirectional traffic tunnels every 150 m (492 ft), alternating on
each side, in one directional traffic tunnels every 300 m (985 ft) on the outer
side.
Connection to the control room which indicates if a fire extinguisher
is taken.
Hydrants and pipes are not prescribed, but if they are installed the following
parameters must be met: 20 L/sec (317 gpm), hydrants every 150 m (492 ft),
reservoir 250 m3 (8,830 ft3).
Germany/RABT 2.5.4.1 (For tunnels > 400 m or 1,312 ft) Two 6 kg (13.2 lb) (net) handheld
extinguishers are placed at each emergency point (distance < 150 m or 492 ft).
2.5.4.2 Tunnels with length 600 m (1,968 ft) (400 m (1,312 ft) at high
HGV traffic > 4,000 HGV × km/tube/day) must be equipped with fire
hydrant... the pipes shall be designed for 1200 L/min (317 gpm) at 6 to 10
bar (87 to 145 psi). The connectors are placed opposite the emergency points
at distances less than 150 m (492 ft).
For tunnels < 400 m (1,312 ft) fire hydrant shall be available at the portals.
Austria/RVS RVS 9.233 Dimension of fire fighting equipment recess.
RVS 9.281 Fire fighting equipment recesses are necessary in tunnels over
500 m. They have to be positioned just opposite the emergency telephone
stations and half way between the emergency telephone stations. Thus they
are on both sides with a = 250 m (820 ft).
RVS 9.282 At each fire fighting equipment recess and at each emergency
telephone station two extinguishers (6 L and 9 L) must be available.
RVS 9.281 Water reservoir of 80 m3 (2,825.2 ft3), refilled in 24 h.
RVS 9.282 Hydrants at each fire fighting equipment recess and at the portals
fed through water main [dry pipe only for tunnels 500 to 1000 m (1,640 to
3,280 ft). Necessary for category III and IV, recommended for all categories.
Capacity 20 L/sec (317 gpm) for 1 h.
Norway/Road 602.205 Fire extinguishers should be at least 6 kg (13.2 lb) ABC and must
Tunnels be located in separate compartments.
602.1 Class B every 250 m (820 ft), C, D every 125 m (410 ft), E every 125 m
(410 ft), F every 62.5 m (205 ft).
602.206 Possible solutions are: separate reservoirs (approximately 6 m3) in
connection with the drainage system, a water tanker vehicle with sufficient
capacity (approximately 6 m3 or 212 ft3) firewater reservoir at the low point
of the tunnel. In special cases where pressurized water is easily available
(e.g., in a tunnel located in a town) a continuous water main can be an
alternative.
(continued on next page)
OCR for page 166
167
TABLE F2-1
(continued )
Country/ Requirement
Guideline
UK/BD78/99 3.26 ...Facilities for ...responding to a fire shall be provided to safeguard all
areas of the tunnel including the tunnel services building.
3.12 Emergency Points ... shall be large enough to house fire-fighting
facilities and emergency roadside telephones connected to... control
centres.... The nominal spacing for emergency points is 50 m (164 ft), with
emergency roadside telephones and fire hose reels... at 100 m (328 ft)
intervals.
Hand held fire extinguishers are normally provided in tunnel class AA, A, B.
To be considered in class C.
Pressurized Fire Hydrants normally provided in tunnel class AA, A, B, C, to
be considered in class D.
Germany/RABT 2.5.4.1 (For tunnels > 400 m or 1,312 ft) Two 6 kg (13.2 lb) (net) handheld
extinguishers are placed at each emergency point (distance < 150 m or 492
ft).
2.5.4.2 Tunnels with length 600 m (1,968 ft) (400 m (1,312 ft) at high
HGV traffic > 4,000 HGV × km/tube/day) must be equipped with fire
hydrant... the pipes shall be designed for 1200 L/min (317 gpm) at 6 to 10
bar (87 to 145 psi). The connectors are placed opposite the emergency points
at distances less than 150 m (492 ft).
For tunnels < 400 m (1,312 ft) fire hydrant shall be available at the portals.
Austria/RVS RVS 9.233 Dimension of fire fighting equipment recess.
RVS 9.281 Fire fighting equipment recesses are necessary in tunnels over
500 m. They have to be positioned just opposite the emergency telephone
stations and half way between the emergency telephone stations. Thus they
are on both sides with a = 250 m (820 ft).
RVS 9.282 At each fire fighting equipment recess and at each emergency
telephone station two extinguishers (6 L and 9 L) must be available.
RVS 9.281 Water reservoir of 80 m3 (2,825.2 ft3), refilled in 24 h.
RVS 9.282 Hydrants at each fire fighting equipment recess and at the portals
fed through water main [dry pipe only for tunnels 500 to 1000 m (1,640 to
3,280 ft)]. Necessary for category III and IV, recommended for all categories.
Capacity 20 L/sec (317 gpm) for 1 h.
Norway/Road 602.205 Fire extinguishers should be at least 6 kg (13.2 lb) ABC and must
Tunnels be located in separate compartments.
602.1 Class B every 250 m (820 ft), C, D every 125 m (410 ft), E every 125
m (410 ft), F every 62.5 m (205 ft).
602.206 Possible solutions are: separate reservoirs (approximately 6 m3) in
connection with the drainage system, a water tanker vehicle with sufficient
capacity (approximately 6 m3 or 212 ft3) firewater reservoir at the low point
of the tunnel. In special cases where pressurized water is easily available
(e.g., in a tunnel located in a town) a continuous water main can be an
alternative.
UK/BD78/99 3.26 ...Facilities for ...responding to a fire shall be provided to safeguard all
areas of the tunnel including the tunnel services building.
3.12 Emergency Points ... shall be large enough to house fire-fighting
facilities and emergency roadside telephones connected to... control
centres.... The nominal spacing for emergency points is 50 m (164 ft), with
emergency roadside telephones and fire hose reels... at 100 m (328 ft)
intervals.
Hand held fire extinguishers are normally provided in tunnel class AA, A, B.
To be considered in class C.
Pressurized Fire Hydrants normally provided in tunnel class AA, A, B, C, to
be considered in class D.
Fire Hose Reels normally provided in tunnel class AA, to be considered in
class A, B, C.
8.55 Automatic fire extinguishing systems are not considered suitable for the
traffic space. Total flood gaseous systems and foam systems are not practical
where people are present in vehicles. Water sprinkler systems may cool
buoyant smoke causing immediate smoke logging of the tunnel and
producing potentially explosive air/vapor mixes.
OCR for page 167
168
TABLE F2-1
(continued )
Country/ Requirement
Guideline
Netherlands/NL- 15.1 nr. 2. For a tunnel there is no need for provisions of fire suppression by
Safe tunnel users, except if the economic value of the tunnel asks for this. Then
fire extinguishers are recommended under the condition that there is
monitoring.
15.2 nr. 5 In tunnels of large economic value and with a mechanical.
ventilation system, hose-reels are recommended. The distance between the
hose-reels must be limited to 60 m (197 ft).
15.2 nr. 6 In first aid stations with hose-reels a fire extinguisher shall also be
provided.
15.3 nr. 12A system of fire fighting consists of a distribution system (hose-
reels), and possibly completed with a system to increase the water pressure
and a system of water feeding.
15.3 nr. 13 If the tunnel has a large economical value consideration has to
be made for the construction of a permanent installation for the increase of
water pressure and a water reservoir.
15.2 nr. 7 A foaming substance shall be added to the extinguishing
medium.
8.3 nr. 6c Fixed fire suppression mitigation systems as sprinklers can be
used for mitigating the heating of the concrete and the reinforcement in the
Netherlands sprinkler system is not yet applied because of disadvantages,
though it will be applied in the tunnel of the `Betuwelijn.'
Sweden In tunnels > 500 m there should be extinguishers at each portal and at least
every 150 m. The extinguisher should meet SS-EN 3-7 requirements. They
should contain 6 kg ABC powder and manage the test fires 34A and 183B.
Hose connections required at each portal and at least every 150 m.
PIARC The minimum content of 6 kg when the traffic includes mainly passenger
cars. The maximum of 9 kg when heavy goods vehicles are numerous.
Extinguisher removal alarms recommended.
For tunnels from 200 to 1000 m long (case based), water supply requirement
is 1000 L/min, 0.5 MPa (standpipe). Hydrants 1002000 m spacing.
UNECE Fire extinguishers should be installed systematically in tunnels and in their
entrances.
Water supply shall be available for fire brigade.
Australia Dry chemical extinguisher (equipment niche, 60 m spacing) and CO2
extinguishers adjacent to all electrical switchboards, control panels.
Hydrants at 60 m spacing (hose reels). Hydrants with fittings located in each
cabinet.
Japan For tunnels Class D (>100 m) two 6 kg extinguishers at 50 m spacing
required.
For tunnels Class A or Class B (>1000 m) water supply requirement is 130
L/min, 0.17 MPa (1.7 kgf/cm2). Hydrants < 50 m spacing.
Korea Two 3.3 kg (>3 Unit Capacity) extinguishers. <50 m spacing. Extinguisher
removal alarms recorded.
NFSC: For tunnels over 1000 m long water supply requirement is 130
L/min, 0.17 MPa (1.7 kgf/cm2). Hydrants < 50 m spacing. Minimum water
discharge time: 20 min.
GIST: For tunnels over 1000 m long water supply requirement is 190 L/min,
0.3 MPa (3 kgf/cm2) Hydrants < 50 m spacing. Minimum water discharge
time: 40 min hose connections less than 50 m for tunnels class 2 or higher
over 1000 m long.
(continued on next page)
OCR for page 168
169
TABLE F2-1
(continued )
Country/ Requirement
Guideline
NFPA 502 (2008 7.8.1 Portable fire extinguishers, with a rating of 2-A:20-B:C, shall be
edition) located along the roadway in approved wall cabinets at intervals of not more
than 90 m (300 ft).
7.8.2 To facilitate safe use by motorists, the maximum weight of each
extinguisher shall be 9 kg (20 lb).
7.8.3 Portable fire extinguishers shall be selected, installed, inspected, and
maintained in accordance with NFPA 10.
Annex J. Fire Apparatus. J.3 Extinguishers. Fire-fighting units should carry
multipurpose, dry chemical extinguishers and an extinguishing agent for
Class D metal fires.
7.7 Standpipe, Fire Hydrants, and Water Supply. Standpipe, fire hydrants,
and water supply systems in road tunnels shall be provided in accordance
with the requirements of Chapter 9.
9.2.1 Wet standpipe systems (automatic or semiautomatic) shall be
connected to an approved water supply that is capable of supplying the
system demand for a minimum of 1 h.
9.2.2 Dry standpipe systems shall have an approved water supply that is
capable of supplying the system demand for a minimum of 1 h.
9.4.1 Hose connections shall be spaced so that no location on the protected
roadway is more than 45 m (150 ft) from the hose connection.
9.4.2 Hose connection spacing shall not exceed 85 m (275 ft).
A.5.3 Where a municipal or privately owned waterworks system is available,
consideration should be given to providing fire hydrants along limited access
highways at spacing not to exceed 305 m (1,000 ft). The minimum required
water supply for fire hydrants should not be less than 3,780 L/min
(1,000 gpm) at 1.4 bar (20 psi) from each of two hydrants flowing
simultaneously.
EU/2004/54/EC 2.10.1 Emergency stations are intended to provide various items of safety
equipment, in particular emergency telephones and extinguishers, but are not
intended to protect road users from the effects of fire.
2.10.2 Emergency stations can consist of a box on the sidewall or preferably
a recess in the sidewall. They shall be equipped with at least an emergency
telephone and two fire extinguishers.
2.10.3 Emergency stations shall be provided near the portals and inside at
intervals which for new tunnels shall not exceed 150 m (492 ft) and which in
existing tunnels shall not exceed 250 m (820 ft).
2.11 Water supply. A water supply shall be provided for all tunnels.
Hydrants shall be provided near the portals and inside at intervals which
shall not exceed 250 m (820 ft). If a water supply is not available, it is
mandatory to verify that sufficient water is provided otherwise.
OCR for page 169
170
F3 Tunnel Fire Detection
Appendix F3 provides comparison tables on tunnel fire smoke detection requirements in different national (including NFPA
502, 2008 edition) and international standards.
TABLE F3
FIRE/SMOKE DETECTION (VENTILATION SENSORS OR SPECIFIC FIRE DETECTION)
(NFPA 502, 56, 77)
Country/ Requirement
Guideline
France/ 3.6 In tunnels where there is no permanent human supervision ... an
Circ2000- automatic fire detection system is required, whenever the ventilation system,
63A2 which is used in the event of a fire, is not that which is automatically brought
into use in the event of serious tunnel pollution... in other cases to be
considered.
Switzerland/ Automatic fire detection system which reacts to the degree of temperature as
Design well as to temperature progress, able to detect a 100 L fuel fire. Connected to
the control room and to the traffic signals, switching them on red in driving
direction towards the fire.
Switzerland/ If mechanical ventilation is applied an automatic smoke detection system is
Ventilation obligatory. Distance between measurement point <300 m (984 ft) (see
separate Guidelines Fire Detection).
Germany/RABT 2.3.6 ... Ventilation sensors...
2.5.3.2 Automatic fire alarm equipment must be installed for tunnel length
over 400 m (1,312 ft) and for tunnels with mechanical ventilation.
2.3.6... As guidance for the sensitivity of the fire detection: a fire of 5 MW
(17 MBtu/hr) shall be observed within half a minute at up to 6 m/s (1,181
fpm) air velocity. The fire shall be localized with an accuracy of 50 m
(164 ft).
Austria/RVS RVS 9.282 Automatic fire detectors in operation rooms and lay by. Generally
in the tunnel if there is a mechanical ventilation system.
UK/BD78/99 Fire detection mentioned for sumps and service buildings only.
Smoke detection.
Netherlands/NL- 14.2 nr. 4 Apply a measurement of visibility for smoke detection...
Safe 14.2 nr. 2 In tunnels with an automatic ventilation system; apply a
measurement of visibility to determine the concentration of NO2. When the
concentration is too high, the system has to activate the automatic ventilation
system.
14.2 nr. 6 Consider the application of measurement of temperature to detect
fire.
14.2 nr. 7 Consider the application of a detection system to detect high risk
explosive gases.
Korea GIST: Manual pull stations (push button) shall be installed around the hydrant
cabinets or inside fire extinguisher cabinets spaced less than 50 m in tunnels
over 500 m long.
An automatic fire detection system is required in tunnels over 500 m long or
Class 3 and higher in bi-directional tunnels and in urban tunnels, or in all
other tunnels over 1000 m long or Class 2.
In tunnels over 2000 m, installation of monitoring system equipped with
CCTV should be considered for detection of smoke and flame from fires. In
tunnels between 500 m and 1000 m automatic fire detection system can be
replaced by the automatic incident detection system.
Japan Manual pull stations (push button) recommended to be installed with
emergency telephones spaced less than 50 m in tunnels longer than Class C.
An automatic fire detection system applied in tunnels longer than 300 m if the
traffic flow is high and tunnels equipped with ventilation system (Class A and
higher).
(continued on next page)
OCR for page 170
171
TABLE F3
(continued )
Country/ Requirement
Guideline
Sweden Alarm push buttons or emergency telephones should be coordinated with the
escape routes. Should be installed on both sides of the tunnel tube if three
lanes or more. Spacing shall be less than 150 m apart for all classes of tunnels.
An automatic fire detection system is required in tunnels class TB and higher.
NFPA 502 7.4.1 At least two systems to detect, identify, or locate a fire in a tunnel shall
(2008 edition) be provided, including one manual, means meeting the requirements of 7.4.1.2
and either a closed-circuit television (CCTV) system in accordance with
7.4.1.3 or an automatic fire detection system in accordance with 7.4.1.4.
7.4.1.2.1 Manual fire alarm boxes mounted in NEMA Enclosure Type 4 (IP
65) or equivalent boxes shall be installed at intervals of not more than 90 m
(300 ft) and at all cross-passages and means of egress from the tunnel.
7.4.1.2.5 The system shall be installed, inspected, and maintained in
compliance with NFPA 72.
7.4.1.3.1 CCTVs with or without traffic-flow indication devices shall be
permitted to identify fires in tunnels with 24-hour supervision.
7.4.1.4 Automatic Fire Detection Systems.
7.4.1.4.1 Automatic fire detection systems installed in accordance with the
requirements of NFPA 72 shall be installed in tunnels where 24-hour
supervision is not provided.
7.4.1.4.3 Where a fire detection system is installed in accordance with the
requirements of 7.4.1.4.1, the system shall be for fire detection only.
7.4.1.4.4 Automatic fire detection systems shall be capable of identifying the
location of the fire within 15 m (50 ft).
7.4.1.4.5 Spot detectors shall have a light that remains on until the device is
reset.
7.4.1.4.6 CCTV systems used for automatic fire detection shall be permitted
when listed for the intended purpose and installed in accordance with the
manufacturers' requirements and NFPA 72.
7.4.1.4.7 Automatic fire detection systems within a tunnel shall be zoned to
correspond with the tunnel ventilation zones where tunnel ventilation is
provided.
PIARC Push button alarms are optional.
An automatic fire detection system can be useful in tunnels that are long or
complicated, especially when dangerous goods are allowed or when it is
necessary to precisely determine the fire location. They can be also helpful in
unmanned tunnels with transverse or semi-transverse ventilation.
EU/2004/54/EC 2.14.2 Automatic fire detection systems shall be installed in all tunnels, which
do not have a control centre, where the operation of mechanical ventilation for
smoke control is different from the automatic operation of ventilation for the
control of pollutants.
OCR for page 171
172
F4 Tunnel Egress
Appendix F4 provides comparison tables on tunnel egress requirements in different national and international standards. It
covers Parallel Escape Tube (Table F4-1), Emergency Cross Passages (Table F4-2), Shelters (Table F4-3), and Direct Pedes-
trian Emergency Exits (Table F4-4).
TABLE F4-1
PARALLEL ESCAPE TUBE (NFPA 502, 56)
Country/ Requirement
Guideline
France/Circ2000- 2.2.2 ... A safety tunnel parallel to the tunnel is only to be constructed if this
63A2 is justified for technical reasons (e.g., pilot tunnel)...
Germany/RABT 2.5.1.3 Escape doors can lead to a rescue tunnel, which can be used by
pedestrians. The tunnel can be parallel to traffic tunnel and various
emergency exits from the tunnel can be connected to a common exit to the
opening. The longitudinal slope shall not be more than 10%; the cross
section shall be 2.25 m × 2.25 m (7.4 ft x 7.4 ft).
Austria/RVS The general safety concept shows two possibilities.
- Limitation of escape routes (according to tunnel cross section) in
combination with natural or longitudinal ventilation.
- Transversal or semi-transversal ventilation with no limitation of escape
routes.
RVS 9.232 Dimension of escape routes 1.20 m x 2.20 m (3.9 ft x 7.2 ft),
doors 1.0 m x 2.0 m (3.3 ft x 6.6 ft).
RVS 9.281 Escape tubes for foot passengers or vehicles could be used to
minimize the escape routes (see above).
Dimensions are given.
UK/BD78/99 2.38 ...A separate service tunnel...should be considered on a whole life cost
basis...Such tunnels may also be used for evacuation purposes during an
emergency.
Netherlands/NL- 11.4 ...Escape tubes must have a minimal width of 1.20 m (3.9 ft).
Safe Narrowing obstacles in escape tubes must be avoided as much as possible;
the width here must still be 0.85 m (2.8 ft) minimal ....The escape route
must be safe (no possible exits in smoking zones, no crossing of lanes with
traffic) ...Avoiding danger of stumbling (no steps).
Korea Required for tunnels over 3000 m with bi-directional traffic or risky uni-
directional tunnels. Can be installed in tunnels over 1000 m long with bi-
directional traffic or urban tunnels with expected congestion.
Australia A separate egress tunnel should be provided in tunnels, particularly with bi-
directional traffic, or in tunnels in which adjacent tunnel cannot be used for
escape purposes. For unidirectional tunnels, escape to adjoining road tunnel
can be considered; however traffic management of the adjoining tunnel is
required
Japan Required for tunnels class AA, and for tunnels class A >3000 m long with
bi-directional traffic and longitudinal ventilation system.
PIARC Escape corridor or escape gallery can be one of evacuation possibilities.
NFPA 502 (2008) Not required
EU/2004/54/EC 2.3.3 ... Examples of such emergency exits are... exits to an emergency
gallery ....
OCR for page 172
173
TABLE F4-2
EMERGENCY CROSS PASSAGE (NFPA 502, 56, 77)
Country / Requirement
Guideline
France/ 2.2 Arrangements for the evacuation and protection of users and emergency
Circ2000- access ... shall be provided on a systematic basis and access shall be provided
63A2 approximately every 200 m (656 ft); a shorter spacing is to be used in tubes
which are frequently congested and which have more than three lanes. In non-
urban tunnels these arrangements are to be provided where lengths exceed 500
m (1,640 ft) and the spacing will be approximately 400 m (1,312 ft).
2.2.2 Communication between the (two) tubes represents a satisfactory
arrangement ... provided that a single door does not provide access from the
tube in which the incident or accident occurred and a traffic lane in the other
tube.
Switzerland/ In two tube tunnels cross passages for pedestrians every 300 m (984 ft), for
Design vehicles every 900 m (2,953 ft). In tunnels with high frequency of dangerous
goods vehicles the following have to be applied: Cross passages have to be
equipped in order to stop fire spread to the other tube.
Emergency exits to a lower level have to be equipped with a ramp instead of
stairways.
Switzerland/ Cross passages with length > 5 m (16.4 ft) need two doors.
Ventilation
Germany/ 2.5.1.3 Escape routes must be indicated and illuminated.
RABT Tunnels 400 m (1,312 ft) must have emergency exits at regular distances
300 m (984 ft). The emergency exits can connect to the other tunnel tube
directly or through a cross passage. Cross passages have doors in both ends.
Austria/RVS RVS 9.233 Dimension and design of cross passages.
RVS 9.281 Opposite each lay by (see S23) a cross passage for vehicles is
situated (a = 1000 m or 3,280 ft).
Additionally in tunnels without fire ventilation and in tunnels with a
longitudinal gradient >3% a foot passenger cross passage is situated at each
emergency call station (a = 250 m or 820 ft).
Norway/Road 409 Cross passages. In tunnels with two parallel tubes pedestrian cross
Tunnels passages between the tubes shall be arranged for escape. These shall be located
for every 250 m (820 ft)...
602.1 Pedestrian cross passages are required for tunnel class E and F.
UK/BD78/99 3.16 Escape Routes: In twin bore tunnels, passenger escape routes through fire
doors positioned in central walls or cross-connecting passages, shall be
provided. These shall be positioned at 100 m (328 ft) nominal intervals...
5.13 (100 m or 328 ft preferred limit, 150 m or 492 ft maximum limit).
3.17 Tunnel Cross Connections: Tunnel cross connections are generally of
three types:
i. A single set of fire doors in the partition wall between two traffic bores,
ii. A cross passage with fire doors at both ends providing a safe refuge and an
escape route from one bore to the other,
iii. Normal provision for class AA, to be considered in class A and B.
Netherlands/ 11.4 Exit-doors for escape are necessary when the distance to open area is too
NL-Safe long. Distance between those exit doors must be determined by quantitative
risk analysis.
Korea GIST: For tunnels over 500 m long or bi-directional tunnels with a parallel
escape tube spacing between cross passages shall not exceed 250 m. For
tunnels less than 1200 m long, spacing can be less than 300 m.
OCR for page 173
174
TABLE F4-2
(continued )
Country / Requirement
Guideline
Japan For uni-directional tunnels over 750 m long spacing shall not exceed 750 m;
for bi-directional tunnels over 400 m long spacing shall not exceed 350 m. The
actual installation distance is 200300 m
Sweden For all tunnels spacing shall not exceed 150 m. The time for escape to portal,
escape route, or other safe haven must not be longer than the tunnel can
evacuate before the conditions become critical. The gradient of an escape route
cannot be higher than 8%. Class TA should have increased fire protection;
e.g., shorter distance between escape routes.
PIARC The most common escape route in two tube tunnels is a connection (cross
passage) between the two tubes. The distance between connections should
depend on traffic density and emergency rescue scenarios; for instance
100200 m in cities.
NFPA 502 7.14.7.1 Where tunnels are divided by a minimum of 2-hour fire-rated
(2008) construction or where tunnels are in twin bores, cross passageways between
the tunnels shall be permitted to be utilized in lieu of emergency exits.
7.14.7.2 The following requirements shall be met:
(1) Cross passageways shall not be farther than 200 m (656 ft) apart.
(2) An emergency egress walkway with a minimum clear width of 1.12 m (3.6
ft) shall be provided on each side of the cross passageways.
(a) Walkways shall be protected from oncoming traffic by either a curb, a
change in elevation, or a barrier.
(b) Walkways shall be continuous the entire length of the tunnel, terminating
at surface grade.
(c) Raised walkways in tunnels shall have guards in accordance with NFPA
101.
(d) Intermediate rails shall not be required for walkway guards.
(3) Where portals of the tunnel are below surface grade, surface grade shall be
made accessible by a stair, vehicle ramp, or pedestrian ramp.
EU/2004/54/EC 2.3.3. Emergency exits allow tunnel users to leave the tunnel without their
vehicles and reach a safe place in the event of an accident or a fire and also
provide access on foot to the tunnel for emergency services. Examples of such
emergency exits are: direct exits from the tunnel to the outside, cross
connections between tunnel tubes, exits to an emergency gallery, shelters with
an escape route separate from the tunnel tube.
2.3.4. Shelters without an exit leading to escape routes to the opening shall not
be built.
2.3.5. Emergency exits shall be provided if an analysis of relevant risks,
including how far and how quickly smoke travels under local conditions,
shows that the ventilation and other safety provisions are insufficient to ensure
the safety of road users.
2.3.6. In any event, in new tunnels, emergency exits shall be provided where
the traffic volume is higher than 2,000 vehicles per lane.
2.3.7. In existing tunnels longer than 1000 m (3,280 ft), with a traffic volume
higher than 2,000 vehicles per lane, the feasibility and effectiveness of the
implementation of new emergency exits shall be evaluated.
2.3.8. Where emergency exits are provided, the distance between two
emergency exits shall not exceed 500 m (1,640 ft).
2.3.9. Appropriate means, such as doors, shall be used to prevent smoke and
heat from reaching the escape routes behind the emergency exit, so that the
tunnel users can safely reach the outside and the emergency services can have
access to the tunnel.
OCR for page 174
175
TABLE F4-3
SHELTERS (NFPA 502)
Country/ Requirement
Guideline
France/ 2.2.2...Whenever none of the preceding arrangements apply, shelters are to
Circ2000- be built to offer users a safe place while they await evacuation. Each shelter
63A2 shall have a surface area of at least 50 m2 (538 ft2)... Shelters must be
connected to the exterior of the tunnel by an access-way, which is protected
from fire and intended for emergency purposes.
UK/BD78/99 3.16 ... Single bore tunnel escape route and safe refuge requirements shall be
examined and established by the Design Organization from first principles, to
the agreement of the TDSCG.
NFPA 502 (2008 Not required
edition)
EU/2004/54/EC 2.3.3.... Examples of such emergency exits are... shelters with an escape
route separate from the tunnel tube.
2.3.4 Shelters without an exit leading to escape routes to the open shall not
be built.
TABLE F4-4
DIRECT PEDESTRIAN EXITS (NFPA 502, 77)
Country/ Requirement
Guideline
France/ 2.2.1 In the case of tunnels where the roadway is less than 15 m (49.2 ft) from
Circ2000- the ground surface ...the facilities for the evacuation and protection of users
63A2 and emergency access shall consist of direct communication with the exterior.
Accessible to pedestrians only, these communication facilities must have a
minimum width of 1.40 m (4.6 ft) and a height of 2.20 m (7.2 ft). ...
Germany/RABT 2.5.1.3. The escape doors can connect directly to the open or to evacuation
shafts, which are vertical structures for escape routes with stairways leading to
the open. Stairways must be a minimum of 1.5 m (4.9 ft) wide. At the design of
shafts the limited physical performance of disabled and elderly people will
have to be considered.
UK/BD78/99 3.17 Tunnel cross connections are generally of three types:
i..., ii..., iii. Access doors to a central escape shaft or passage, leading to a
safe exit.
Netherlands/NL- 11.4 Avoid staircases where possible. When necessary to provide, then
Safe minimum width: 0.7 m (2.3 ft)/minimum height: 1.9 m (6.2 ft).
NFPA 502 7.14.6.1 Emergency exits shall be provided throughout the tunnel spaced not
(2008 edition) more than 300 m (1,000 ft) apart.
7.14.6.2 The emergency exits shall be enclosed in a minimum 2-hour fire-
rated enclosure having a Class A interior finish as defined in NFPA 101
(see also cross passages requirements).
EU/2004/54/EC 2.3.3... Examples of such emergency exits are...direct exits from the tunnel to
the outside...
OCR for page 175
176
F5 Tunnel Incident Response
Appendix F5 provides comparison tables on tunnel incident response requirements in different national and international stan-
dards. It covers a Separate Emergency Vehicle Gallery Access (Table F5-1), Cross Passage Rescue Vehicular Access (Table F5-
2), Emergency Lane (Table F5-3), Direct Pedestrian Emergency Access (lateral upstairs shaft) (Table F5-4), Turning Areas
(Table F5-5), and Emergency Services Station at Portals (Table F5-6).
TABLE F5-1
SEPARATE EMERGENCY VEHICLE GALLERY ACCESS (NFPA 502)
Country/ Requirement
Guideline
NFPA 502 Not required
(2008
edition)
France/ 2.2.2 In tunnels more than 5000 m (3.1 mi) long, which are not light traffic tunnels,
Circ2000- the safety tunnel parallel to the tunnel or the access-ways providing access to the
63A2 shelters must be capable of being used by the motor-driven equipment.
Germany/ 2.5.1.3 In exceptional cases it can be reasonable to construct the evacuation tunnel
RABT so that it can be used by rescue vehicles. This may be relevant for tunnels longer
than 300 m (984 ft) with high traffic load. The need for this arrangement shall be
documented as part of safety concept.
Austria/ RVS 9.281 Could be used to minimize the ways for rescue staff. According to this,
RVS the tunnel category could be influenced.
TABLE F5-2
CROSS PASSAGE RESCUE VEHICULAR ACCESS (NFPA 502, 56)
Country/ Requirement
Guideline
France/ 2.3.1...In tunnels more than 1000 m (3,280 ft) long, provision must be made
Circ2000- at approximately every 800 m (2,625 ft) for the passage of emergency
63A2 vehicles from one tube to the other if there are two tubes ...
Germany/RABT 2.5.1.3. ... For two tube tunnels every third cross passage can be constructed
for the use of fire fighting and rescue vehicles, in case this is required by the
safety and rescue concept. ...
Austria/RVS RVS 9.233 Dimension and design of cross passages.
RVS 9.281 At every second emergency call station (a = 500 m or 1,640 ft)
a cross passage for rescue staff vehicles is situated.
Korea GIST: For tunnels over 500 m long or bi-directional tunnels with a parallel
escape tube spacing for ambulances shall not exceed 750 m.
NFPA 502 (2008 Not required
edition)
EU/2004/54/EC 2.4.1 In twin-tube tunnels where the tubes are at the same level or nearly,
cross connections shall be suitable for the use of emergency services at least
every 1500 m (4,921 ft).
OCR for page 176
177
TABLE F5-3
EMERGENCY LANE (NFPA 502)
Country/ Requirement
Guideline
France/ 2.1.1 - Emergency vehicle access widths. If traffic is one-way, the transverse
Circ2000- profile must be designed to permit access by emergency vehicles, including in
63A2 the normal traffic direction, when there are stopped vehicles on the nominal
number of traffic lanes. Exceptions... if there is direct communication with the
exterior...
- if there is access to a second tube ... and also if the traffic can easily be
interrupted in the second tube...
Switzerland/ In bidirectional traffic tunnels > 1.5 km (4,921 ft) emergency bays every 600
Design to 900 m (1,968 ft), alternating on each side, every 2 to 3 km turning bays
(6,562 to 9,842 ft).
Design of emergency bay.
Germany/RABT 2.5.1.1 Under certain economical and traffic conditions it can be reasonable to
have an emergency lane--to be evaluated and documented...
2.5.1.2 Emergency bays shall be considered when the construction of
emergency lanes is not reasonable. They are required at a tunnel length of
600900 m (1,968 to 2,953 ft)... The distance shall be 600 m (1,968 ft) in
each traffic direction.
Austria/RVS RVS 9.232 Necessity and dimensions of emergency lanes in accordance to
speed, traffic volume, number of lanes, and traffic regulation systems.
RVS 9.233 Dimension and design of lay by.
RVS 9.281 Lay by a = 1000 m (3,280 ft), in tunnels with two directional traffic
on both sides, positioned together with emergency call.
NFPA 502 Not required
(2008 edition)
UK/BD78/99 3.14 Due to the high costs involved there are very few examples of continuous
emergency stopping lanes within tunnels.
However, additional lane width or widened verges provide a temporary
expedient for traffic to be able to pass a stranded vehicle.... The first priority
and whole basis of safe tunnel operation must always be to remove, as a
matter of urgency, any obstacle to unrestricted lane use.
Normal provision for tunnel class AA, A, B.
TABLE F5-4
DIRECT PEDESTRIAN ACCESS (LATERAL, UPSTAIRS, SHAFT) (NFPA 502)
Country/ Requirement
Guideline
Netherlands/NL- 11.3 To support the rescue teams it is strongly recommended to locate the
Safe escape doors (from two tubes to the escape tube in the middle) opposite to one
another.
Appendix: The width of escape routes is based on width of the stretcher with a
nurse accompanying on the side. The width of the doors must support easily
the width of the stretcher.
EU/2004/54/EC 2.3.3 Emergency exits allow tunnel users to leave the tunnel without their
vehicles and reach a safe place in case of an accident or a fire and also provide
an access on foot to the tunnel for emergency services. Examples of such
emergency exits are: direct exits from the tunnel to the outside, cross
connections between tunnel tubes, exits to an emergency gallery, shelters with
an escape route separate from the tunnel tube.
OCR for page 177
178
TABLE F5-5
TURNING AREAS (NFPA 502, 56)
Country/ Requirement
Guideline
France/ 2.3.1...In tunnels more than 1000 m (3,280 ft) long, provision must be made
Circ2000- at approximately every 800 m (2,625 ft) for... them to turn round...
63A2
Switzerland/ In bidirectional traffic tunnels > 1.5 every 23 km turning bays.
Design
Germany/RABT 2.5.6 Turning bays are standard equipment for tunnels > 900 m (2,953 ft), to
be considered for tunnels 600 to 900 m (1,968 to 2,953 ft).
Austria/RVS RVS 9.233 Dimension of turning areas.
RVS 9.281 In category III and IV tunnels (see 4.4) with two-directional traffic,
a turning area is necessary instead of each fourth lay by. Alternatively an
escape tube for vehicles could be situated.
Norway/Road 408.1 ...Turning bays are arranged in tunnels with contra flow traffic. Lay bys
Tunnels function as turning bays for cars. Turning bays for larger vehicles are arranged
as specified in figures... Normal distances between turning bays (for large
vehicles) in class B, C and D are 2000 m (6,562 ft), 1500 m (4,921 ft), and
1000 m (3,280 ft).
Korea GIST: For tunnels over 1000 m long, spacing between turning areas shall not
exceed 750 m. Emergency stopping lanes can be used as turning areas.
NFPA 502 No requirements
(2008 edition)
UK/BD78/99 3.19 Turning Bays: In tunnels of over 5 km (3.1 mi) length, turning bays of
sufficient size to enable a truck to turn around shall be provided, not more than
1 km (3,280.8 ft) from the middle of the tunnel.
To be considered in class AA.
TABLE F5-6
EMERGENCY SERVICES STATION AT PORTALS (NFPA 502)
Country/ Requirement
Guideline
France/ 2.3.2 A location 12 m (39.4 ft) long and 3 m (9.8 ft) wide for parking an
Circ2000- emergency vehicle shall be provided outside, close to the ends...
63A2 In addition to this ... an arrangement enabling emergency vehicles to turn
around/move from one roadway to another shall be provided externally, close
to the portals.
UK/BD78/99 3.20 Emergency Services Parking: If necessary, an area close to the tunnel
portals shall be provided for the parking of police and emergency services
vehicles and equipment when attending a tunnel incident.