From page 302...
... 5.3 The control equipment should be so designed that any failure of the following equipment will prevent continued operations and cause the fuel supply to be cut off. 5.3.1 Safety thermostat/draught failure 5.3.1.1 A flue gas temperature controller, with a sensor placed in the flue gas duct, should be provided that will shut down the burner if the flue gas temperature exceeds the temperature set by the manufacturer for the specific design.
From page 303...
... If flame is not established within 10 s, the fuel supply to the burners should be immediately shut off automatically. 5.3.2.4 Whenever the flame safeguard control has operated because of failure of ignition, flame failure or failure of any component, only one automatic restart may be provided.