From page 306...
... A1.2 Type approval test should include measuring of the following parameters: Max. capacity Pilot fuel consumption O2 average in combustion chamber/zone CO average in flue gas Soot number average Combustion chamber flue gas outlet temperature average kW or kcal/h kg/in of specified waste kg/in per burner kg/in per burner % mg/MJ Bacharach or Ringelman scale °C Amount of unburned % by weight components in ashes
From page 307...
... This type of waste contains up to 70% moisture, up to 5% incombustible solids and has a heating value range of about 2,300 kJ/kg as fired.
From page 308...
... A1.5 Required emission standards to be verified by type approval test O2 in combustion chamber 6-12% CO in flue gas maximum average Soot number maximum average Unburned components in ash residues Combustion chamber flue gas outlet temperature range 200 mg/MJ Bacharach 3 or Ringelman 1 (a higher soot number is acceptable only during very short periods such as starting up)
From page 309...
... chamber (spot checks only) ; control/monitor temperature in combustion chamber flue gas outlet.